Energy measurements

So we measured the power over a period of 70 minutes (longer than the slowest test run), and calculated the real energy (power x time) consumed.

Hyper-V total energy running one vApusmark tile

You can see that with the exception of the Xeon X5670 running with the high performance plan, there is almost no difference between the L5640 measurements and the “balanced” X5670.  And let us look at performance now. We made a geometric mean of the number of URL/s and the number of database transactions that the server was able to process.

Hyper-V throughput

 

This graph explains why the Xeon X5670 does so well: as it is able to handle more transactions and web requests per second, it can empty the queues more quickly. When the web request and database queues are empty, the CPU can throttle back and save power.  Since  the idle power of the Xeon X5670 is pretty low (almost as good as the idle power of the low power version), this is a real tangible advantage.

Response time

At the end of day, users will not complain about throughput, they experience high response times as disturbing. Responses times are the ones that are part of the SLAs. Let us see what we measured. We made a geometric mean of the response time of the database queries and web requests.

Hyper-V 
Response time

The results are stunning! Despite the fact that we do not max out the CPUs at all, the X5670 leaves the low power version far behind when it comes to response times. This is partly due to the fact that vApus Mark I is constructed as a CPU test. In your own datacenter you might not see the same results if you are (partly) I/O constrained of course. But if web and database applications are well cached, the higher performing CPU can deliver tangible lower response times.

Average power and energy Trading off performance and power
Comments Locked

49 Comments

View All Comments

  • has407 - Thursday, July 15, 2010 - link

    Good points. At the datacenter level, the IT equipment typically consumes 30% or less of the total power budget; for every 1 watt those servers etc. consume, add 2 watts to your budget for cooling, distribution, etc.

    Not to mention that the amortized power provisioning cost can easily exceed the power cost over the life of the equipment (all that PD equipment, UPS's etc cost $$$), or that high power densities have numerous secondary effects (none good, at least in typical air-cooled environments).

    I guess it really depends on your perspective: a datacenter end customer with a few racks (or less); a datacenter volume customer/reseller; a datacenter operator/owner; or a business who builds and operates your own private datacenters? Anadtech's analysis is really more appropriate for the smaller datacenter customer, and maybe smaller resellers.

    Google published "The Datacenter as a Computer -- An Introduction to the Design of Warehouse-Scale Machines" which touches on many of the issues you mention, and should be of interest to anyone building or operating large systems or datacenters. It's not just about Google and has an excellent set of references; freely available at::

    http://www.morganclaypool.com/doi/abs/10.2200/S001...
  • Whizzard9992 - Monday, July 19, 2010 - link

    Very cool article. Bookmarked, though I'm not sure I'll ever read the whole thing. Scanning for gems now. Thanks!
  • gerry_g - Thursday, July 15, 2010 - link

    Just a little engineering clarification, one pays for electricity via energy units, not voltage, amperage or even power. Power is an instantaneous measurement, over time.

    Electrical energy is almost universally measured/billed in KWh Kilo Watts x hours). Power plants and some rare facilities may use Mega Watt hours.

    Why does it make a difference? Actual voltage not only has different standards but there are distribution loses. For example, nominal US 240/120V (most common on newer utility services) may droop considerably. However, in the US, if the building is fed via a three phase supply, nominal will be 208/120 volts!

    That meter that measures the energy you pay for measures real power multiplied by time regardless of single phase, three phase, nominal voltage or voltage loses in the distribution system.

    Most modern computer power supplies are fairly insensitive to reasonable variations in supply voltage. They have about the same power efficiency at high or low voltage. Thus they will consume the same wattage based given the same load regardless of present voltage.

    Since we measure computer power supplies in Watts (capitalized since the unit is named or abbreviated after a persons name as is Volt and AMP or W, V and A). Wh (hours are not named after a person) is the most consistent base unit for energy consumption.

    Watts of course are directly converted to units of heat, thus the air conditioning costs are somewhat directly computable.

    Just trivia but consistent ;)
  • gerry_g - Thursday, July 15, 2010 - link

    I should clarify, Watts are NOT voltage times amperage in AC systems! Watts represent real power (billable and real heat). reactive and non-linear components generally draw greater amperage than is billed for if one just multiplies V x A! Look at a power supply sticker, it has a wattage rating and a VA (Voltage x Amperage) rating that do not match!

    Also note, UPS systems have different VA and Wattage ratings!

    For this reason, costs can only be computed by Watts x Time. (KWh as an example), not Voltage or Amperage.
  • has407 - Friday, July 16, 2010 - link

    Hmm.... If your Watts come with power distribution, UPS, cooling and amortization, then maybe "costs can only be computed by Watts x Time".

    If not, I think you're going to go broke rather quickly, at least allowing for ~1.25x for power distribution, ~1.5x for UPS, ~2x for cooling, and ~3x for CAPEX/amortization.

    Would you settle at 12x your Watts for mine (in volume of course and leaving me a bit of margin)? Counter offer anyone?
  • has407 - Thursday, July 15, 2010 - link

    True, but as Johan posted earlier, he's looking at it from the datacenter customer perspective, and amps is how it's typically priced, because that's how it's typically provisioned.

    The typical standard datacenter rate sheet has three major variables if you're using your own hardware: rack space, network, and power. Rack space is typically RU's with a minimum of 1/4 rack. Network is typically flat rate at a given speed, GB/mo or some combination thereof. Power is typically 110VAC at a given amperage, usually in 5-10A increments (at least in the US). You want different power--same watts but 220 instead of 110? Three-phase? Most will sell it to you, but at an extra charge because they'll probably need a different PDU (and maybe power run) just for you.

    They don't generally charge you by the Watt for power, by the bit for network, or anything less than a 1/4 rack because the datacenter operators have to provision in manageable units, and to ensure they can meet SLAs. They have to charge for those units whether you use them or not because they have to provision the infrastructure based on the assumption that you will use them. (And if you exceed them, be prepared for nasty notes or serious additional charges.)

    Those PDU's, UPS's, AC units, chillers, etc. don't care if you only used 80% of your allotted watts last month--they had to be sized and provisioned based on what you might have used. That's a fixed overhead that dwarfs the cost of the watts you actually used, that the datacenter operator had to provision and has to recover. If you want/need less than that, some odd increment or on-demand, then you go to a reseller who will sell you a slice of a server, or something like Amazon EC2.

    If it makes people feel better (at least for those in the US), simply consider the unit of power/billing as ~396KWH (5A@110VA/mo) or ~792KWH (10A@110VAC/mo). Then multiply by 3, because that's the typical amount of power that's actually used (e.g., for distribution, cooling and UPS) above and beyond what your servers consume. Then multiply that by the $/KWH to come up with the operating cost. Then double it (or more) because that's the amortized cost of all those PDU's, UPS's and the cooling infrastructure in addition to the direct costs of electricity you're using.

    In short, for SMB's who are using and paying for colo space and have a relatively small number of servers, the EX Xeon's may make sense, whereas those operating private datacenters or a warehouse full of machines may be better served by LP's.
  • gerry_g - Friday, July 16, 2010 - link

    >True, but as Johan posted earlier, he's looking at it from the datacenter customer perspective, and amps is how it's typically priced, because that's how it's typically provisioned.

    Not true at least in the US or UK. Electricity is priced in KWh. Circuit protection is rated (provisioned) by Amps. (a simple Google search or electricity price or cost will reveal that).

    Volts x Amps is not equal to Wattage for most electronics. Thus VxAxHours is not what one is billed for.
  • JarredWalton - Friday, July 16, 2010 - link

    You're still looking at it from the residential perspective. If you colocate your servers to a data center, you pay *their* prices, not the electric company prices, which means you don't just pay for the power your server uses but you also pay for cooling and other costs. Just a quick example:

    Earthnet charges $979 per month for one rack, which includes 42U of space, 175GB of data, 8 IP addresses, and 20 Amps of power use. So if you're going with the 1U server Johan used for testing, each server can use anywhere from 168W to ~300W, or somewhere between 1.46A and 2.61A. For 40 such servers in a rack, you're looking at 58.4A to 104A worst-case. If you're managing power so that the entire rack doesn't go over 60A, at Earthnet you're going to pay and extra $600 per month for the additional 40A. This is all in addition to bandwidth and hardware costs, naturally.

    In other words, Earthnet looks to charge business customers roughly $0.18 per Wh, but it's a flat rate where you pay the full $0.18 per Wh for the entire month, assuming a constant 2300W of power draw (i.e. 20A at 115VAC). In reality your servers are probably maxing out at that level and generally staying closer to half the maximum, which means your "realistic" power costs (plus cooling, etc.) work out to nearly $0.40 per kWh.
  • Penti - Saturday, July 17, 2010 - link

    Data centers aren't exactly using a 400V/240V residential connection. It's 10/11/20 or even 200 kV and their own transformers or so. And of course megawatts of power.

    Inside the datacenter it's all based on the connections and amps available though. You just can't have an unlimited load on a power socket from a PDU. And it's mostly metered.
  • gerry_g - Thursday, July 15, 2010 - link

    Humor intended...

    The average human outputs ~300 BTU/hour of heat and significant moisture. Working from home will cut the server facilities air conditioning bill by lowering the heat and humidity the AC system needs to remove!